Freight Allowed by State |
||||
---|---|---|---|---|
$3000 | $4000 | $5000 | $6000 | |
Alabama | Arkansas | Missouri | Connecticut | Arizona |
Florida | Delaware | New Jersey | Maine | California |
Georgia | Illinois | New York | Massachusetts | Colorado |
North Carolina | Indiana | Ohio | New Hampshire | Idaho |
South Carolina | Iowa | Oklahoma | Rhode Island | Minnesota |
Tennessee | Kansas | Pennsylvania | Vermont | Montana |
Kentucky | Texas | Nebraska | ||
Louisiana | Virginia | Nevada | ||
Maryland | West Virginia | New Mexico | ||
Michigan | Wisconsin | North Dakota | ||
Mississippi | Oregon | |||
South Dakota | ||||
Utah | ||||
Washington | ||||
Wyoming |
Showing all 4 results
Catalog No. | P56-1GR | P56-2GR | P56-3GR |
ANSI Class | 56-1 | 56-2 | 56-3 |
Dimensions (inches) | |||
Diameter | 7-1/2 | 9 | 10-1/2 |
Height | 5-3/4 | 6-1/2 | 7-1/2 |
Leakage Distance | 13 | 17 | 21 |
Dry Arcing Distance | 7 | 8-1/4 | 9-1/2 |
Minimum Pin Height | 6 | 7 | 8 |
Mechanical Values (Ultimate)* |
|||
Cantilevel Strength (Ibs.) | 2,500 | 3,000 | 3,000 |
Electrical Values (kV) |
|||
Typical Voltage Class | 23 | 23 | 34.5 |
Low Frequency Dry Flashover | 95 | 110 | 125 |
Low Frequency Wet Flashover | 60 | 70 | 80 |
Impulse Flashover, Positive | 150 | 175 | 200 |
Impulse Flashover, Negative | 190 | 225 | 265 |
Low Frequency Puncture Voltage | 130 | 145 | 165 |
Radio Influence Voltage Data |
|||
Test Voltage, RMS to Ground (kV) | 15 | 22 | 30 |
Maximum RIV at 1000 kHz (kV) | 100 | 100 | 200 |
Packing & Shipping Data |
|||
Net Weight Each(Ibs.) | 7 | 9.5 | 15 |
Packed Weight Each (Ibs.) | 8.8 | 12.5 | 19 |
Standard Package Quantity | 6 | 2 | 2 |
*rus accepted
*Maximum recommended working load = 40% of cantilever rating
GR=Gray glaze, Radio – Treated
&Standard 1-3/8″ Diameter Threads